Seeco Logo Banner


Dimensional Data 115 - 230 kV, Type 1GA and 1GLA

 

Plan View - Single Phase

 

 

Elevation View - Installed Switch

Elevation View - Single Phase

 

If the addition of a loadbreak device is not anticipated, dimension "G" may be reduced; consult the factory for special phase spacing requirements

Dimension in Inches (Unless Otherwise Specified)

kV A B C D E F G J K
115 73 49-5/16 168-3/16 91-1/8 147-1/4 51-3/4 18'-0" 35'-0" 16'-0"
138 80-3/4 57-1/16 180-7/16 98-7/8 170-3/4 60-3/4 22'-0" 35'-0" 16'-0"
161 88-1/2 64-3/4 198-7/16 106-5/8 179-3/4 68-3/4 24'-0" 35'-0" 16'-0"
230 106 82-5/16 231-1/2 122 206 85-7/8 28'-0" 40'-0" 16'-0"