Dimensional Data 115 – 230 kV, Type 1G and 1GL |
Plan View – Single Phase
|
Elevation View – Installed Switch If the addition of a loadbreak device is not anticipated, dimension “G” may be reduced; consult the factory for special phase spacing requirements |
Elevation View – Single Phase |
Dimension in Inches (Unless Otherwise Specified)
kV | A | B | C | D | E | F | G | H | J | K | L |
115 | 73 | 49-5/16 | 42-5/8 | 91-1/8 | 103-3/8 | 51-3/4 | 18′-0″ | 9′-0″ | 35′-0″ | 16′-0″ | 48 |
138 | 80-3/4 | 57-1/16 | 52-1/2 | 98-7/8 | 128-3/8 | 60-3/4 | 22′-0″ | 11′-0″ | 35′-0″ | 16′-0″ | 108 |
161 | 88-1/2 | 64-3/4 | 72 | 106-5/8 | 134-7/8 | 68-3/4 | 24′-0″ | 12′-0″ | 35′-0″ | 16′-0″ | 109 |
230 | 106 | 82-5/16 | 96 | 122 | 199-1/2 | 85-7/8 | 28′-0″ | 14′-0″ | 35′-0″ | 16′-0″ | 127 |